OXA-ED — Electric heating

Mycond OXA-ED unit — electric heating

Electric heating (OXA-ED). Built around heavy-duty electric heating elements with precise stepped output control. This is the answer for sites with no hot water circuit and no gas connection — a power supply is all it needs.

Features

  • ⚡ Electric heating elements with stepped control, synchronised with the fan
  • 🌀 Vortex distribution, blades driven by a Belimo actuator
  • 🌬️ EBM-papst fan, stepless VAV control
  • 📶 OXA-V / V2 terminal, OXA-T2 sensors, Modbus RTU
  • 🛡️ Over-voltage, over-current, phase control, power failure and soft start protection

Technical data

ModelOXA-ED-IOXA-ED-II
Fan speed, rpm0~9000~860
Recirculated air flow, m³/h0~67000~9700
Voltage, V380±5%380±5%
Electrical power (fan), kW0~0.850~1.80
Current, A0~1.650~3.60
Recommended mounting height, m4~104~17
Control modeStepless VAV control
Heater controlSynchronisedSynchronised
Sound level, dB<60<60

Dimensions and drawings

Dimension, mmOXA-ED-IOXA-ED-II
A9001100
B12001505
C735920
E100100
F150150
G480568
H765935
J170180
K400400
Weight, kg120170

Heating capacity table

ModelHeater ratingQ, kWts at 10 °Cts at 15 °Cts at 20 °C
OXA-ED-I30~45 kW25.50~38.2522~30 °C24~34 °C26~39 °C
OXA-ED-II35~65 kW29.75~55.2521~33 °C23~36 °C27~40 °C

Legend: Q — heating capacity · ts — supply air temperature. Maximum supply air temperature: 60 °C · maximum ambient temperature: 40 °C.

Non-standard versions (explosion-proof, anti-corrosion, with air purification and other functional sections) are available on request. If the mounting height falls outside the permitted range, please contact the manufacturer.

Request a quotation

Tell us the floor area, the ceiling height and the heat source you already have — an engineer will send back a model selection, a specification and pricing within one working day.

    Or go straight to us: +48 502 121 436 · info@aklimapolska.pl