Hot water heating (OXA-D). The classic high-efficiency option: it runs off district heating, a boiler house or a heat pump, which keeps running costs low and the installation dependable. A recirculating air heater with a vortex diffuser — and no ductwork.
Features
- 🔥 Copper-and-aluminium water coil
- 🌀 Vortex distribution, guide blades with Belimo actuator (0–90°)
- ♻️ Recirculation: draws the overheated air back down from ceiling level
- 🌬️ EBM-papst fan, stepless VAV control 0–100 %
- 🌡️ Temperature sensors on the inlet and on the supply air
- 📶 OXA control unit, OXA-V / V2 terminal, OXA-T2 sensors, Modbus RTU
- 🧽 Automatic dust removal by back-flushing
Technical data
| Model | OXA-D-I | OXA-D-II |
|---|---|---|
| Fan speed, rpm | 0~900 | 0~860 |
| Recirculated air flow, m³/h | 0~6700 | 0~9700 |
| Voltage, V | 380±5% | 380±5% |
| Electrical power, kW | 0~0.85 | 0~1.80 |
| Current, A | 0~1.65 | 0~3.60 |
| Recommended mounting height, m | 4~10 | 4~17 |
| Control mode | Stepless VAV control | |
| Sound level, dB | <60 | <60 |
Dimensions and drawings
| Dimension, mm | OXA-D-I | OXA-D-II |
|---|---|---|
| A | 900 | 1100 |
| B | 990 | 1165 |
| C | 735 | 850 |
| E | 100 | 100 |
| F | 150 | 150 |
| G | 480 | 568 |
| H | 765 | 935 |
| J | 601 | 724 |
| K | 521 | 644 |
| N (female thread) | DN32 | DN40 |
| Weight, kg | 130 | 176 |
| Water volume, l | 5.8 | 9.8 |
Water supply and return connections are on the underside of the casing. DWG drawings are in the Downloads section.
Heating capacity table
| Water temperature, °C | Model | Q, kW (10 °C) | ts, °C | Q, kW (15 °C) | Q, kW (20 °C) |
|---|---|---|---|---|---|
| 90/70 | D-I | 66 | 43 | 61 | 56 |
| 80/60 | D-I | 57 | 39 | 52 | 47 |
| 70/50 | D-I | 46 | 34 | 42 | 38 |
| 60/40 | D-I | 38 | 29 | 33 | 28 |
| 90/70 | D-II | 103 | 43 | 96 | 88 |
| 80/60 | D-II | 88 | 37 | 81 | 74 |
| 70/50 | D-II | 74 | 33 | 66 | 59 |
| 60/40 | D-II | 59 | 28 | 51 | 44 |
Legend: Q — heating capacity · ts — supply air temperature · mw — water volume flow · Δpw — water pressure drop. The 10/15/20 °C columns give the temperature of the recirculated air.
Maximum working pressure: 800 kPa · maximum supply air temperature: 60 °C · maximum ambient temperature: 40 °C. Full tables with water flow rates and pressure drops are in the PDF catalogue.
Non-standard versions (explosion-proof, anti-corrosion, with air purification, increased cooling capacity and other functional sections) are available on request through your regional sales representative. Where the mounting height falls outside the stated range, the unit is built to individual specification.
Request a quotation
Tell us the floor area, the ceiling height and the heat source you already have — an engineer will send back a model selection, a specification and pricing within one working day.