Gas-fired heating (OXA-GD). A high-efficiency, self-contained option with an integral gas burner and combustion chamber for sites with no hot water circuit. Heat is recovered at the top of the unit, giving a thermal efficiency of 98.9 %.
Features
- 🔥 Integral gas burner and combustion chamber
- ♻️ Heat recovery at the top of the unit, efficiency η = 98.9 %
- 🎚️ Modulating gas flow and fan speed control
- 🌀 Vortex air distribution straight into the occupied zone
- 📶 OXA-V / V2 terminal, OXA-T2 sensors, Modbus RTU
Technical data
| Parameter | OXA-GD |
|---|---|
| Fan speed, rpm | 0~860 |
| Recirculated air flow, m³/h | 0~10,600 |
| Voltage, V | 380±5% |
| Electrical power, kW | 0–1.85 |
| Current, A | 0–3.9 |
| Recommended mounting height, m | 4–17 |
| Heating capacity, kW | 0–54.75 |
| Gas consumption, m³/h | 5.21 (operating conditions) / 5.64 (standard conditions) |
| Thermal efficiency, η | 98.9 % |
| Gas inlet pressure, kPa | 5–10 |
| Working pressure, kPa | 2 |
| Control mode | Modulating gas flow and fan speed |
| Sound level, dB | <60 |
Dimensions and drawings
| Dimension, mm | OXA-GD |
|---|---|
| A | 1100 |
| B | 1385 |
| C | 850 |
| E | 100 |
| F | 150 |
| H | 935 |
| J | 170 |
| K | 120 |
| M (flue) | DN80 |
| N (elbow, male thread) | DN20 |
| Weight, kg | 240 |
If you have additional non-standard requirements, talk to our sales team or technical specialists. Where the mounting height falls outside the permitted range, the unit is built to individual specification.