Horizontal discharge with cooling (OXA-SK). The universal build for wall or side mounting with a horizontally directed air stream, covering both heating and cooling. A purpose-designed coil, a high-efficiency droplet eliminator and a drain pan with reliable discharge keep moisture out of the space entirely.
Features
- 🔥 Hot water heating · ❄️ chilled water cooling (7/12, 8/14, 10/16 °C)
- ➡️ Throw distance: up to 19 / 28 m in cooling, up to 17 / 26 m in heating
- 💧 Droplet eliminator, drain pan and discharge connection
- 🌬️ EBM-papst fan, stepless VAV control
- 📶 OXA-V / V2 terminal, OXA-T2 sensors, Modbus RTU
Technical data
| Model | OXA-SK-I | OXA-SK-II |
|---|---|---|
| Fan speed, rpm | 0~900 | 0~860 |
| Recirculated air flow, m³/h | 0~6700 | 0~9900 |
| Voltage, V | 380±5% | 380±5% |
| Electrical power, kW | 0~0.85 | 0~1.80 |
| Current, A | 0~1.65 | 0~3.60 |
| Throw distance, cooling, m | <19 | <28 |
| Throw distance, heating, m | <17 | <26 |
| Control mode | Stepless VAV control | |
| Sound level, dB | <60 | <60 |
Dimensions and drawings
| Dimension, mm | OXA-SK-I | OXA-SK-II |
|---|---|---|
| A | 900 | 1100 |
| B | 1220 | 1300 |
| C | 500 | 700 |
| E | 570 | 570 |
| F | 100 | 92 |
| G | 117 | 204 |
| H | 167 | 268 |
| M (female thread) | DN40 | DN50 |
| N (male thread, condensate) | DN25 | DN32 |
| P | 647 | 695 |
| Q | 765 | 935 |
| Weight, kg | 191 | 250 |
| Water volume, l | 5.8 | 9.8 |
Heating performance
| Water temperature, °C | Model | Q, kW (10 °C) | Q, kW (15 °C) | Q, kW (20 °C) |
|---|---|---|---|---|
| 90/70 | SK-I | 61 | 54 | 47 |
| 80/60 | SK-I | 52 | 46 | 40 |
| 70/50 | SK-I | 42 | 36 | 30 |
| 90/70 | SK-II | 105 | 95 | 80 |
| 80/60 | SK-II | 97 | 88 | 78 |
| 70/50 | SK-II | 90 | 80 | 70 |
Cooling performance (7/12 °C)
| tal, °C | rh, % | Model | Q, kW | ts, °C | mc, l/h |
|---|---|---|---|---|---|
| 24 | 50 | SK-I | 19 | 15.5 | / |
| 26 | 50 | SK-I | 27 | 15.0 | 2.9 |
| 26 | 70 | SK-I | 43 | 16.5 | 29.7 |
| 28 | 70 | SK-I | 50 | 17.5 | 37.4 |
| 24 | 50 | SK-II | 29 | 15.5 | / |
| 26 | 50 | SK-II | 43 | 14.5 | 7.1 |
| 26 | 70 | SK-II | 68 | 16.0 | 48.1 |
| 28 | 70 | SK-II | 79 | 17.0 | 60.6 |
Legend: tal — inlet air temperature · rh — relative humidity · Q — cooling capacity · ts — supply air temperature · mc — condensate flow. Maximum working pressure 800 kPa.
Request a quotation
Tell us the floor area, the ceiling height and the heat source you already have — an engineer will send back a model selection, a specification and pricing within one working day.
Or go straight to us: +48 502 121 436 · info@aklimapolska.pl