Series with air dehumidification (OXA-DK). A ceiling climate unit built to pull humidity down in spaces with heavy moisture loads — swimming pools, wet production areas and storage. It uses a high-efficiency cooling coil to condense moisture out of the air, a pan to collect and drain the condensate, and an optional heating stage to keep the space at a comfortable temperature.
Features
- 💧 Active dehumidification through the unit’s own coil
- 🔥 Heating to hold the room temperature setpoint
- 🛡️ Protects materials and the building fabric from condensation and damp
- 🌀 Vortex distribution, stepless VAV control
- 📶 OXA-V / V2 terminal, OXA-T2 sensors, Modbus RTU
Technical data
| Model | OXA-DK-I | OXA-DK-II |
|---|---|---|
| Fan speed, rpm | 0~900 | 0~860 |
| Recirculated air flow, m³/h | 0~5800 | 0~8500 |
| Voltage, V | 380±5% | 380±5% |
| Electrical power, kW | 0~0.85 | 0~1.80 |
| Current, A | 0~1.65 | 0~3.60 |
| Permitted mounting height, m | 4~13 | 4~21 |
| Control mode | Stepless VAV control | |
| Sound level, dB | <60 | <60 |
Dimensions and drawings
| Dimension, mm | OXA-DK-I | OXA-DK-II |
|---|---|---|
| A | 900 | 1100 |
| B | 1590 | 1734 |
| C | 720 | 920 |
| E | 100 | 100 |
| F | 95 | 95 |
| G | 480 | 568 |
| H | 765 | 935 |
| J | 997 | 1075 |
| K | 1217 | 1323 |
| L | 1457 | 1583 |
| M | 617 | 703 |
| N | 567 | 654 |
| P (female thread) | DN25 | DN32 |
| Q (female thread) | DN40 | DN50 |
| R (male thread) | DN25 | DN32 |
| Weight, kg | 180 | 260 |
| Water volume, l | 12.9 | 18.1 |
Performance tables
| Heating mode (recirculated air 26 °C) | Q, kW | ts, °C | mw, l/h | Δpw, kPa |
|---|---|---|---|---|
| 80/60, DK-I | 21 | 26 | 903 | 2 |
| 80/60, DK-II | 47 | 26 | 1806 | 6 |
| Cooling mode, chilled water 7/12 °C | Q, kW | ts, °C | mc, l/h | mw, l/h |
|---|---|---|---|---|
| 26 °C / 47 % rh, DK-I | 41 | 26 | 29 | 7052 |
| 26 °C / 47 % rh, DK-II | 76 | 26 | 55 | 13,072 |
Legend: Q — capacity · ts — supply air temperature · mc — condensate flow · mw — water volume flow · Δpw — water pressure drop. Maximum working pressure 800 kPa.
Request a quotation
Tell us the floor area, the ceiling height and the heat source you already have — an engineer will send back a model selection, a specification and pricing within one working day.
Or go straight to us: +48 502 121 436 · info@aklimapolska.pl